Orange County NC Website
DocuSign Envelope ID: 989208A2-AC78-4885-B25B-F162607F73BE <br /> Combustion air flow <br /> Exhaust gas temperature at manifold outlet <br /> Fuel consumption at 25%, 50%, 75% and 100% rated output, for both prime and standby ratings <br /> Emissions data for 100% rated output <br /> Location of nearest manufacturer's agent for service and maintenance <br /> The following data relating to the generator shall be submitted with the proposal: <br /> 1. Manufacturer, prime and standby ratings, and catalog number or series number <br /> 2. Outline drawing showing physical dimensions <br /> 3. Radiated heat <br /> 4. Waveform deviation factor and telephone influence factor <br /> The following data relating to the transfer switch, line breaker, and generator breaker shall be <br /> submitted with the proposal: <br /> 1. Manufacturer, rating, and catalog number or series number <br /> 2. Outline drawing showing physical dimensions <br /> 3. Control descriptive data and schematic diagram <br /> The following data relating to the weatherproof housing shall be submitted with the proposal: <br /> 1. Manufacturer, size, and catalog number or series number <br /> 2. Outline drawing showing physical dimensions <br />