Jan 08 1410:43a Aquatic Resource Group 704-583-0730 p.5 <br /> 2. PRODUCTS <br /> 2.01 GENERAL <br /> A. Ultraviolet Disinfection Equipment: Shall operate within the UVC electromagnetic spectrum emitting <br /> wavelengths in the range of 200nm to 400nm. This required wavelength will provide constant <br /> disinfectionlinactivation of bacteria, algae, molds,viruses and destruction of Monochloramines, <br /> Trichloramines,and Dichloramines. Ultraviolet Lamp/Chamber and Spectra Touch Control Panel by <br /> Engineered Treatment Systems (Telephone 920-885-4628, Fax 920-885-4386)or Architect/Engineer <br /> approved equal.Any deviation/exception must be provided in writing to and approved by the designer no less <br /> than ten days prior to the bid date. <br /> B. The UV System shall have an MET or equivalent(ETL, GSA, or UL)listing, be NSF-50 2010 certified including <br /> Section 13 and 3rd party validated to the USEPA UVDGM 2006 Guidelines. <br /> 1. Equipment General Description <br /> a. The Ultraviolet System shall be provided in a complete package to include: 316L Stainless Steel <br /> Chamber,Spectra Touch Control System located in a NEMA 12 rated panel, Medium Pressure <br /> Bulb(s)designed to emit wavelengths within the UVC electromagnetic spectrum,strainer basket <br /> automatic wiper system,and Project Commissioning by a Certified ETS Ultraviolet Technician. <br /> 2.02 UNIT TYPES— <br /> ECP Units: Ultraviolet manufacturer tD offer unit capability of a horizontal OR vertical installation application <br /> using state of art design and direct flow through characteristics. Direct flow will be required in order to reduce <br /> total head loss through the system. Unit shall be a Single Lamp medium pressure system with a bulb of 1.3 <br /> kW power range. ANSI flange of 3"and flow pattern of up to 260 GPM @ 95% UVT,Any systems validated or <br /> designed for flows based on 98% UVT are not acceptable- Chamber and Control Cabinet shall be as indicated <br /> on the drawings. The electrical requirements include either 208 or 220 volt single-phase power with a 20 amp <br /> external breaker. All required electrical work to be performed by licensed electrician. <br /> ETS Model ECP-113-5 single phase 22D volt validated flow rate of 260 GPM or equal unit <br /> ECF Units: Ultraviolet manufacturer to offer unit capability of a horizontal OR vertical installation application <br /> using state of art design and direct flow through characteristics. Direct flow will be required in order to reduce <br /> total head loss through the system, Unit shall be a Multiple Lamp medium pressure system with a bulb range <br /> of(2) 1.0 kW—(4)3.0 kW power range. Multiple lamp system is required in order to maintain quality <br /> disinfection in the event of a single bulb failure. ANSI flange range of 4"—12"and flow pattern of 360 to 37DO <br /> GPM. @ 95% UVT.Any systems validated or designed for flows based on 98% UVT are not acceptable. <br /> Chamber and Control Cabinet shall be as indicated on the drawings. Electrical requirements to include either <br /> of the following 208,240,480 or 575 volt 3-phase with a (XX)amp external breaker recommended by ETS <br /> based on the appropriate supply voltage.The electrical contractor is to take into account plus/minus 3%for <br /> external breaker. All required electrical work to be performed by licensed electrician. <br /> ETS Model ECF 220-8 3 phase 480 volt validated flow rate of 1100 gpm or equal unit <br /> ETS Model ECF 215-6 3 phase 480 volt validated flow rate of 665 gpm or equal unit <br /> 2.03 ULTRAVIOLET CHAMBER <br /> A. Pressure rated for 100 psi(tested to 150 psi), and pressure drop across the unit will be minimal. The unit <br /> shall be constructed of 316L stainless steel passivated to prevent corrosion within the harsh pool Environment. <br /> The Ultraviolet chamber shall come complete with the following equipment: <br /> B. Ultraviolet intensity monitor factory calibrated to provide intensity in mw1cm2 , monitors providing percentage <br /> of lamp output not acceptable. It must include a built-in alarm system to notify operator when output level <br /> drops below required level of 60 mj/cm2 for indoor pools or 40mj/cm2 for outdoor pools(or operator set <br /> dosing levels). <br />