Orange County NC Website
MCC 7500 Trunked Resources 2.TEST <br /> Step 1. Using a shorting wire,simulate a relay <br /> closure on an input via the punch block. <br /> Step 2. Verify that CONSOLE-1 momentary <br /> 1.DESCRIPTION input displays the icon designated for an <br /> ON—STATE- <br /> The alarm inputs of the Aux 110 can be Step 3. Remove the shorting wire and verity that <br /> connected to almost any device that requires or CONSOLE-1 displays the icon <br /> can detect a relay closure. These signals can designated for an OFF STATE. <br /> be simulated and monitored in the factory. <br /> Step 4. Connect the meter to the pins to monitor <br /> a relay output <br /> SETUP <br /> Step 5. Verify that the meter reads an open <br /> circuit <br /> Connect a multi-meter capable of monitoring <br /> closures to the proper pins of the punch block Step 6. Press the output button on the console <br /> cabled to the Aux 1/0.One momentary input and to initiate a relay closure. <br /> one momentary output should be configured on <br /> at least one MCC 7500 console. Step 7. Verity that the meter displays a dosed <br /> CONSOLE-1 -TALKGROUP 1 circuit- <br /> CONSOLE-1 -SITE-CONSITE 1 <br /> Aux WO punch block pinout: <br /> Aux VO 1 -pins 26,1 <br /> Aux 1/0 2-pins 27,2 <br /> Aux VO 3-pins 28,3 <br /> Aux YO 4-pins 29,4 <br /> VERSION#1.030 Pass_Fall <br /> Orange County,North Carolina <br /> MCC 7500 Console System Use or disclosure of this proposal is subject <br /> to the restrictions on the cover page. <br /> Motorola Solutions Confidential Restricted Acceptance Test Plan 3-3 <br />