Orange County NC Website
Drawing P1.1: <br />o Plan 1/P1.1: Add new 3-inch vent at Staff Toilet 139. <br />o Detail 2/P1.1: Relocate plumbing fixtures in Toilet 130 to agree with Architectural plan; <br />add 2-inch vent at floor drain P6 in Lab 131. <br />o Detail 3/P1.1: Relocate plumbing fixtures in Staff Toilet 139 to agree with Architectural <br />plan. <br />o Detail 4/P1.1: Relocate plumbing fixtures in Family Toilet 106 to agree with <br />Architectural plan. Provide ADA-compliant drinking fountain in place of relocated <br />fixture in corridor outside Nutritionist 1056. <br />• Drawing P4.0: Add fixture P7 to Plumbing Fixture Schedule & Specifications. <br />ATTACHMENTS: <br />Sketches SDA-001, SDA-002, SKA 3.3 (revised) <br />Drawings A1.6, C2.0, C2.1, P1.1, P4.0 <br />REQUES ED BY THE ARCHITECT: <br />vid L. Browne, AIA CSI CCS LEED AP <br />Project Architect <br />X OWNER X ARCHITECT X CONSULTANT X CONTRACTOR X FIELD X OTHER (Inspections) <br />